FORM 201.24-EG1 (701)YCWSWATER COOLED LIQUID CHILLER91 TONS THROUGH 216 TONS320 kW THROUGH 760 kW60HzSTYLE A
10YORK INTERNATIONAL110100100 1000 10000110100100 1000Pressure DropsFIGURE 1 - COOLER WATER PRESSURE DROP CURVES (ENGLISH)YCWS Model Number
FORM 201.24-EG111YORK INTERNATIONAL110100100010100110100100010 100FIGURE 2 - COOLER WATER PRESSURE DROP CURVES (SI)YCWS Model Number Cooler0
12YORK INTERNATIONALGUIDE TO SELECTIONComplete water chilling capacity ratings for YORK YCWSchillers are shown on the following pages to cover themajo
FORM 201.24-EG113YORK INTERNATIONALSAMPLE SELECTIONWater Cooled Condenser (YCWS)GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and0.0001 evaporator
14YORK INTERNATIONALRatings (R-22 English)NOTES:1. Tons = Unit Cooling Capacity Output2. kW = Compressor Input Power3. MBH = Condenser heat rejection4
FORM 201.24-EG115YORK INTERNATIONALYCWS0200SCYCWS0220SCYCWS0240SCIPLV = 21.8IPLV = 20.8IPLV = 21.2NOTES:1. Tons = Unit Cooling Capacity Output2. kW =
16YORK INTERNATIONALRatings (R-22 SI)NOTES:1. KWo = Unit kW Cooling Capacity Output2. KWi = Compressor kW Input3. COP = Coefficient of Performance4. L
FORM 201.24-EG117YORK INTERNATIONALNOTES:1. KWo = Unit kW Cooling Capacity Output2. KWi= Compressor kW Input3. COP = Coefficient of Performance4. LCWT
18YORK INTERNATIONALRatings- Brine (30 % Ethylene Glycol) (R-22 English)NOTES:1. Tons = Unit Cooling Capacity Output2. kW = Compressor Input Power3. M
FORM 201.24-EG119YORK INTERNATIONALNOTES:1. Tons = Unit Cooling Capacity Output2. kW = Compressor Input Power3. MBH = Condenser heat rejection4. EER =
2YORK INTERNATIONALNomenclatureYC W S 0140 S C 46 Y A YC= York ChillerW= Water cooledS= Screw
20YORK INTERNATIONALRatings- Brine (30 % Ethylene Glycol) (R-22 SI)NOTES:1. KWo = Unit kW Cooling Capacity Output2. KWi = Compressor kW Input3. COP =
FORM 201.24-EG121YORK INTERNATIONALNOTES:1. KWo = Unit kW Cooling Capacity Output2. KWi = Compressor kW Input3. COP = Coefficient of Performance4. LCW
22YORK INTERNATIONALRatings- Brine (30 % Propylene Glycol) (R-22 English)NOTES:1. Tons = Unit Cooling Capacity Output2. kW = Compressor Input Power3.
FORM 201.24-EG123YORK INTERNATIONALNOTES:1. Tons = Unit Cooling Capacity Output2. kW = Compressor Input Power3. MBH = Condenser heat rejection4. EER =
24YORK INTERNATIONALRatings- Brine (30 % Propylene Glycol) (R-22 SI)NOTES:1. KWo = Unit kW Cooling Capacity Output2. KWi = Compressor kW Input3. COP =
FORM 201.24-EG125YORK INTERNATIONALNOTES:1. KWo = Unit kW Cooling Capacity Output2. KWi = Compressor kW Input3. COP = Coefficient of Performance4. LCW
26YORK INTERNATIONALPart Load RatingsRated in accordance with ARI Standard 550/590EnglishYCWS0100SC Load Tons kW EER 1.0 91.3 72.0 15.2 0.8 68.5 51.
FORM 201.24-EG127YORK INTERNATIONALRated in accordance with ARI Standard 550/590SIYCWS0100SC Load kWo kWi COP100% 321.1 72.0 4.5 75% 240.8 51.5 4.7 50
28YORK INTERNATIONALPhysical DataMODEL YCWS 0100SC 0120SC 0140SC 0180SC 0200SC 0220SC 0240SCGeneral Unit Data Nominal Unit Capacity (Tons) 91 110 131
FORM 201.24-EG129YORK INTERNATIONALABCUnit PanelDWeight Distribution by Model1" Isolator Selections - VMC Type CP-4- X Model A B C DYCWS0100S
FORM 201.24-EG13YORK INTERNATIONALYORK YCWS Water-Cooled models provide chilled water for all air conditioning applications thatuse central station ai
30YORK INTERNATIONALIsolator Details1” ISOLATOR DETAILSNEOPRENE ISOLATOR DETAILSTYPE MAX LOAD DEFL. SPRING& SIZE
FORM 201.24-EG131YORK INTERNATIONALSound DataSound Pressure Levels (SPL), dB re 20 microPa inaccordance with ARI Standard 575-94Note: All ‘A’ weighted
32YORK INTERNATIONALDimensions (English) Center of gravity (inches) Model X Y ZYCWS0100SC 57 21 34YCWS0120SC 58 22 34YCWS0140SC 57 22 34YCWS0180
FORM 201.24-EG133YORK INTERNATIONALDIMENSIONSNOTES:1. CLEARANCES - Recommended YORK clearancesto service the unit are as follows:Rear to Wall: 1’ 8”Fr
34YORK INTERNATIONALAll dimensions are in mm unless otherwise noted. Mounting Dimensions (mm) Model AA BB CCYCWS0100SC 2937 864 603YCWS0120SC 2937 86
FORM 201.24-EG135YORK INTERNATIONALNOTES:1. CLEARANCES - Recommended YORK clearancesto service the unit are as follows:Rear to Wall: 508mmFront to Wal
36YORK INTERNATIONALElectrical DataMULTIPOINT POWER SUPPLY (SEE FIG 9 , PAGE 30)SYSTEM #1(Each of the two field provided power supply circuits individ
FORM 201.24-EG137YORK INTERNATIONALYCWS0100SC 175 200 225 300 140 404YCWS0120SC 227 250 300 400 181 591YCWS0140SC 227 250 300 400 181 591YCWS0180SC -1
38YORK INTERNATIONALElectrical Data - Cont.SINGLE POINT POWER SUPPLY (SEE FIG 10 & 11 , PAGE 30 & 31)(One field provided power supply circuit
FORM 201.24-EG139YORK INTERNATIONALIncoming Wire Range Selections MODEL VOLT TERM
4YORK INTERNATIONALGENERALThe Liquid Chiller will be completely assembled with allinterconnecting refrigerant piping and internal wiring,ready for fie
40YORK INTERNATIONALIncoming Wire Range Selections (Cont.)MULTIPOINT WIRING SYSTEM #1YCWS0100SC #2 - 4/0 AWG # 8 - 2 AWG #4 - 300 KCM # 6 - 1/0 AWG #6
FORM 201.24-EG141YORK INTERNATIONALMULTIPOINT WIRING SYSTEM #2YCWS0100SC #2 - 4/0 AWG # 8 - 2 AWG #4 - 300 KCM # 6 - 1/0 AWG #6 - 350 KCM # 6 - 1/0 AW
42YORK INTERNATIONALFIGURE 9 - MULTIPOINT POWER SUPPLY CONNECTION - STANDARD UNITFIGURE 10 - SINGLE POINT POWER SUPPLY WITH INTERNAL CIRCUIT BREAKER
FORM 201.24-EG143YORK INTERNATIONALFIGURE 11 - OPTIONAL SINGLE POINT POWER SUPPLY WITH INTERNAL CLASS J FUSES/BLOCKLEGENDTERM BLOCK TERMINAL BLOCK (FA
44YORK INTERNATIONALTypical Control Panel Wiring
FORM 201.24-EG145YORK INTERNATIONAL
46YORK INTERNATIONALUNIT LOCATIONChillers may be placed on the ground floor or upper floorof the building. The floor must be level and capable ofsuppo
FORM 201.24-EG147YORK INTERNATIONALYORK Model YCWS ______ Packaged Chiller(s). The(each) unit shall have a cooling capacity of ______ tonswith Compres
48YORK INTERNATIONALeach unit. All piping will be ACR copper with brazed joints.The liquid line will include: a shutoff valve with chargingport; sight
FORM 201.24-EG149YORK INTERNATIONAL
FORM 201.24-EG15YORK INTERNATIONALThe Power and Control Panel shall be divided into a powersection for each electrical system, a common input sec-tion
50YORK INTERNATIONAL
FORM 201.24-EG151YORK INTERNATIONAL
Form 201.24-EG1 (701)New ReleaseRPC 3M 701 4.16Codes: DXS, ET
6YORK INTERNATIONALoverride for servicing.Print - Operating data or system fault shutdown historyfor last six faults. Printouts through an RS-232 port
FORM 201.24-EG17YORK INTERNATIONALALTERNATIVE REFRIGERANTS - Contact your nearest YORK of-fice for information and availability on alternative HFC ref
8YORK INTERNATIONALDesign ParametersMin. Cooler Water Flow - l/sec 12.6 12.6 12.6 16.4 16.4 18.9 18.9Max. Cooler Water Flow - l/sec 31.9 31.9 31.9 43.
FORM 201.24-EG19YORK INTERNATIONALLow-pressure liquid refrigerant enters the cooler tubes and is evaporated and superheated by the heat energy absorbe