FORM 150.64-EG1 (505)
AIR-COOLED
SCROLL CHILLERS
STYLE D
YCAL0041 – YCAL0065
50 AND 60HZ
47 – 60 TON
165 – 210 KW
R-22
Zobrazit stránku 0
1 2 3 4 5 6 ... 79 80

Shrnutí obsahu

Strany 1 - SCROLL CHILLERS

FORM 150.64-EG1 (505)AIR-COOLEDSCROLL CHILLERSSTYLE DYCAL0041 – YCAL006550 AND 60HZ47 – 60 TON165 – 210 KWR-22

Strany 2 - Table of Contents

YORK INTERNATIONAL10This page intentionally left blank.

Strany 3 - Introduction

YORK INTERNATIONAL11FORM 150.64-EG1GUIDE TO SELECTIONCapacity ratings for YORK YCAL Packaged Air-Cooled Liquid Chillers, shown on pages 16 through 39

Strany 4 - Specification

YORK INTERNATIONAL12 a. 56.1 Tons b. 55.9 Compressor KW c. 10.7 Unit EER4. Calculate Compressor kW at 50 Tons: 5. Calculate GPM: 6.

Strany 5 - MILLENNIUM CONTROL CENTER

YORK INTERNATIONAL13FORM 150.64-EG1NOTES:1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirem

Strany 6

YORK INTERNATIONAL14Water Pressure DropNote: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for mini

Strany 7 - Options and Accessories

YORK INTERNATIONAL15FORM 150.64-EG1Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum

Strany 8

YORK INTERNATIONAL16NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)3

Strany 9

YORK INTERNATIONAL17FORM 150.64-EG1NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control

Strany 10 - YORK INTERNATIONAL

YORK INTERNATIONAL18NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)3

Strany 11 - Selection Data

YORK INTERNATIONAL19FORM 150.64-EG1NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control

Strany 12

YORK INTERNATIONAL2        

Strany 13 - Design Parameters

YORK INTERNATIONAL20Ratings - R-22 (60Hz - SI Units)NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans,

Strany 14 - Water Pressure Drop

YORK INTERNATIONAL21FORM 150.64-EG1NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control

Strany 15 - flow points

YORK INTERNATIONAL22Ratings - R-22 (50Hz - English Units)NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors,

Strany 16 - R-22 (60Hz - English Units)

YORK INTERNATIONAL23FORM 150.64-EG1NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control

Strany 17 - MODEL: YCAL0051EC

YORK INTERNATIONAL24Ratings - R-22 (50Hz - English Units) - Cont.NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compr

Strany 18 - MODEL: YCAL0065EC

YORK INTERNATIONAL25FORM 150.64-EG1NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control

Strany 19

YORK INTERNATIONAL26Ratings - R-22 (50Hz - SI Units)NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans,

Strany 20 - R-22 (60Hz - SI Units)

YORK INTERNATIONAL27FORM 150.64-EG1NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and the control

Strany 21

YORK INTERNATIONAL28Part Load Ratings - R-22 (English Units)YCAL0041 % FULL LOAD DISPL.TONS KWAmbient °FUNIT EER100.0 35.0 38.2 95.0 9.675.0 28.2 24.

Strany 22 - R-22 (50Hz - English Units)

YORK INTERNATIONAL29FORM 150.64-EG1Part Load Ratings - R-22 (SI)YCAL0041 % FULL LOAD DISPL.KWCompKWAmbient °CUNITCOP100.0 123.0 38.2 35.0 2.875.0 99.

Strany 23

YORK INTERNATIONAL3FORM 150.64-EG1YORK Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications using central station ai

Strany 24

YORK INTERNATIONAL30Physical Data YCAL Model No.Dimension General Unit Data Nominal Compressor Capacity Condenser Condenser Fans, Low Sound Condenser

Strany 25

YORK INTERNATIONAL31FORM 150.64-EG1YCAL Model No.Dimension General Unit Data Nominal Compressor Capacity Condenser Condenser Fans, Low Sound Condenser

Strany 26 - R-22 (50Hz - SI Units)

YORK INTERNATIONAL32Sound Data60Hz Line FrequencyLow Noise Fan R-2263 125 250 500 1000 2000 4000 8000 dBAYCAL0041 92 91 92 90 86 81 77 74 92 YCA

Strany 27

YORK INTERNATIONAL33FORM 150.64-EG150Hz Line FrequencyLow Noise Fan R-2263 125 250 500 1000 2000 4000 8000 dBAYCAL0041 88 87 88 87 83 78 74 71 88YCAL

Strany 28 - R-22 (English Units)

YORK INTERNATIONAL34Dimensions - YCAL0041 (English)NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation)

Strany 29 - Part Load Ratings - R-22 (SI)

YORK INTERNATIONAL35FORM 150.64-EG190 9/16"45 5/16"YCGX1 1/16"ORIGINEND CAPWIDTH21 13/16"TOP VIEW9 13/16"1 1/16"9 13/16&

Strany 30 - Physical Data

YORK INTERNATIONAL36Dimensions - YCAL0045 (English)VIEW B-B3 15/16"3 1/4"6 3/4"BOTTOM OF PANEL 7/8" TYP.47 3/4"46 15/16"

Strany 31

YORK INTERNATIONAL37FORM 150.64-EG190 9/16"45 5/16"YCGX1 1/16"ORIGINEND CAPWIDTH20 1/16"TOP VIEW9 13/16"1 1/16"9 13/16&q

Strany 32 - Sound Data

YORK INTERNATIONAL38Dimensions - YCAL0051 (English)VIEW B-B3 15/16"3 1/4"6 3/4"BOTTOM OF PANEL 7/8" TYP.47 3/4"46 15/16"

Strany 33

YORK INTERNATIONAL39FORM 150.64-EG190 9/16"45 5/16"YCGX1 1/16"ORIGINEND CAPWIDTH20 1/16"TOP VIEW9 13/16"1 1/16"9 13/16&q

Strany 34 - YCAL0041 (English)

YORK INTERNATIONAL4SpecificationGENERALThe 47 - 60 Ton (165 - 210 kW) YCAL models are shipped complete from the factory ready for installati

Strany 35 - CONTROL PANEL

YORK INTERNATIONAL40Dimensions - YCAL0055EC - (English)VIEW B-B3 15/16"3 1/4"6 3/4"BOTTOM OF PANEL 7/8" TYP.62 5/8"61 7/8&quo

Strany 36 - YCAL0045 (English)

YORK INTERNATIONAL41FORM 150.64-EG190 9/16"45 5/16"YCGX1 1/16"ORIGINEND CAPWIDTH18 7/16"TOP VIEW9 13/16"1 1/16"9 13/16&q

Strany 37

YORK INTERNATIONAL42Dimensions - YCAL0061 (English)VIEW B-B3 15/16"3 1/4"6 3/4"BOTTOM OF PANEL 7/8" TYP.62 5/8"61 7/8"43

Strany 38 - YCAL0051 (English)

YORK INTERNATIONAL43FORM 150.64-EG190 9/16"43 5/16"YCGX1 1/16"ORIGINEND CAPWIDTH16 11/16"TOP VIEW9 13/16"1 1/16"9 13/16&

Strany 39

YORK INTERNATIONAL44Dimensions - YCAL0065 (English)62 5/8"61 7/8"34 11/16"15 3/4"9 15/16"43 1/8"12 5/8"3" VICT

Strany 40 - YCAL0055EC - (English)

YORK INTERNATIONAL45FORM 150.64-EG190 9/16"43 5/16"16 11/16"38"5 3/16"153 5/8"15 1/16"16"25 3/8"28 9/16&q

Strany 41 - PANEL

YORK INTERNATIONAL46NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rat

Strany 42 - YCAL0061 (English)

YORK INTERNATIONAL47FORM 150.64-EG123011150YCGX28ORIGINEND CAPWIDTH554TOP VIEW2492824914 DIA MOUNTING HOLES(typ)3678383355TWO LIFTING HOLES BOTH SIDES

Strany 43

YORK INTERNATIONAL48Dimensions - YCAL0045 (SI)VIEW B-B10082171BOTTOM OF PANEL22 TYP.12131192114632176 VICTAULIC (typ)2292 BASE WIDTHLEFT ENDLIQUID OUT

Strany 44 - YCAL0065 (English)

YORK INTERNATIONAL49FORM 150.64-EG123011150YCGX28ORIGINEND CAPWIDTH509TOP VIEW2492824914 DIA MOUNTING HOLES(typ)3678383355TWO LIFTING HOLES BOTH SIDES

Strany 45 - 9 13/16"

YORK INTERNATIONAL5FORM 150.64-EG1MILLENNIUM CONTROL CENTERAll controls are contained in a NEMA 3R/12 (and equivalent to IP55*) cabinet with h

Strany 46 - Dimensions - YCAL0041 (SI)

YORK INTERNATIONAL50Dimensions - YCAL0051 (SI)VIEW B-B10082171BOTTOM OF PANEL22 TYP.12131192114632176 VICTAULIC (typ)2292 BASE WIDTHLEFT ENDLIQUID OUT

Strany 47

YORK INTERNATIONAL51FORM 150.64-EG123011150YCGX28ORIGINEND CAPWIDTH509TOP VIEW2492824914 DIA MOUNTING HOLES(typ)3678383355TWO LIFTING HOLES BOTH SIDES

Strany 48 - Dimensions - YCAL0045 (SI)

YORK INTERNATIONAL52Dimensions -YCAL0055 (SI)VIEW B-B10082171BOTTOM OF PANEL22 TYP.15901572114632176 VICTAULIC (typ)2292 BASE WIDTHLEFT ENDLIQUID OUT8

Strany 49

YORK INTERNATIONAL53FORM 150.64-EG123011151YCGX28ORIGINEND CAPWIDTH468TOP VIEW2492824914 DIA MOUNTING HOLES(typ)3678383356TWO LIFTING HOLES BOTH SIDES

Strany 50 - Dimensions - YCAL0051 (SI)

YORK INTERNATIONAL54Dimensions - YCAL0061 (SI)VIEW B-B10082171BOTTOM OF PANEL22 TYP.15901572109532176 VICTAULIC (typ)2292 BASE WIDTHLEFT ENDLIQUID OUT

Strany 51

YORK INTERNATIONAL55FORM 150.64-EG123011100YCGX28ORIGINEND CAPWIDTH424TOP VIEW R124928 R2249 L1 L214 DIA MOUNTING HOLES(typ)3678383356TWO LIFTING HOLE

Strany 52 - Dimensions -YCAL0055 (SI)

YORK INTERNATIONAL56Dimensions - YCAL0065 (SI)15901572880401252109532176 VICTAULIC (typ)ELECTRICAL ACCESS PANEL2292 BASE WIDTHLEFT ENDLIQUID OUTLIQUID

Strany 53

YORK INTERNATIONAL57FORM 150.64-EG123011100YCGX28ORIGINEND CAPWIDTH424TOP VIEW R124928 R2249 L1 L214 DIA MOUNTING HOLES(typ)3678383356TWO LIFTING HOLE

Strany 54 - Dimensions - YCAL0061 (SI)

YORK INTERNATIONAL58Isolator SelectionsFOR UNITS WITH ALL POINT LOADS LESS THATN 1404 LBS (637 KG)Weight Range (lbs) Weight Range (kg)Model Number Col

Strany 55

YORK INTERNATIONAL59FORM 150.64-EG1Weight Range (lbs)Weight Range (kg)Model Number ColorUp to 751 lbs Up to 341 kg ND-C Yellow751 to 1651 lbs 341 to 7

Strany 56 - Dimensions - YCAL0065 (SI)

YORK INTERNATIONAL6Provisions are included for: pumpdown at shutdown; optional remote chilled water temperature reset and two steps of demand lo

Strany 57

YORK INTERNATIONAL60Isolator Details (cont'd)ENGLISHSIZE H T D E L HCL W HCW MBD2-C2 8 1/2 3/8 5/8 1 3/8 14 12 1/4 5 1/4 3 1/ 2

Strany 58 - Isolator Selections

YORK INTERNATIONAL61FORM 150.64-EG1INTENTIONALLY LEFT BLANK

Strany 59

YORK INTERNATIONAL62Electrical Data1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the r

Strany 60 - (cont'd)

YORK INTERNATIONAL63FORM 150.64-EG1LEGEND ACR-LINE ACROSS THE LINE START C.B. CIRCUIT BREAKER D.E. DUAL ELEMENT FUSE DISC SW DISCONNECT SWITCH

Strany 61 - INTENTIONALLY LEFT BLANK

YORK INTERNATIONAL64Electrical Data - 60HzYCAL0041 - YCAL0065SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)(One Field Provided Power Supply to

Strany 62 - Electrical Data

YORK INTERNATIONAL65FORM 150.64-EG1YCAL0041 - YCAL0065SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)(One Field Provided Power Supply to the chi

Strany 63 - VOLTAGE RANGE

YORK INTERNATIONAL66Electrical Data - 50HzMODELYCAL VOLTMCA1MIN N/F DISC SW2D.E. FUSE CKT. BKR.5FIELD WIRING LUGS6 FIELD WIRING LUGS6 FIELD WIRING L

Strany 64 - Electrical Data - 60Hz

YORK INTERNATIONAL67FORM 150.64-EG1MODELYCAL VOLTMCA1MIN N/F DISC SW2D.E. FUSE CKT. BKR.5FIELD WIRING LUGS6 FIELD WIRING LUGS6 FIELD WIRING LUGS6 S

Strany 65 - YCAL0041 - YCAL0065

YORK INTERNATIONAL68Power WiringFIG. 1 – STANDARD POWER SUPPLY WIRING – (YCAL 0014 - 0080)

Strany 66 - Electrical Data - 50Hz

YORK INTERNATIONAL69FORM 150.64-EG1FIG. 1 – STANDARD POWER SUPPLY WIRING – (YCAL 0014 - 0080)

Strany 67

YORK INTERNATIONAL7FORM 150.64-EG1Options and AccessoriesPOWER OPTIONS:COMPRESSOR POWER CONNECTIONS – Single-point (YCAL0041-0065) terminal block

Strany 68 - Power Wiring

YORK INTERNATIONAL70

Strany 69

YORK INTERNATIONAL71FORM 150.64-EG1CTB1211320131413FLOW SWREMOTE START/STOPPWM INPUTLOAD LIMIT INPUT** Factory wired with optional transformer.Control

Strany 70

YORK INTERNATIONAL72Application DataUNIT LOCATIONThe YCAL chillers are designed for outdoor installation. When selecting a site for installation, be g

Strany 71 - Control Wiring

YORK INTERNATIONAL73FORM 150.64-EG1Typical Piping for Brazed-PlateCoolers Notes:1. Placement on a level surface free of obstructions (including sno

Strany 72 - Application Data

YORK INTERNATIONAL74Guide SpecificationsPART 1 – GENERAL1.01 SCOPE A. The requirements of the General Conditions, Sup-plementary Conditions, Divisi

Strany 73 - Pressure

YORK INTERNATIONAL75FORM 150.64-EG1 2. Refrigerant flow through the compressor with 100% suction cooled motor. 3. Large suction side free volume

Strany 74 - Guide Specifications

YORK INTERNATIONAL76 liquid temperature cutout, low suction pressure cutout, high discharge pressure cutout, anti-re- cycle timer (compressor sta

Strany 75

YORK INTERNATIONAL77FORM 150.64-EG1of N.E.C.) can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be sup

Strany 76

YORK INTERNATIONAL78water sensors, and liquid line components (solenoid valves, filter driers, sight glasses, and TXVs), as discrete elements

Strany 77

YORK INTERNATIONAL79FORM 150.64-EG1

Strany 78

YORK INTERNATIONAL8chilling below 30°F (-1°C) leaving brine temperature for YCAL0041 - 0065 models. Option includes resized thermal expansion va

Strany 79

ALL RIGHTS RESERVEDP.O.Box 1592 York, Pennsylvania USA 17405-1592Copyright © by York International Corporation 2004Subject to change without notice. P

Strany 80 - Codes: DXL, ET2

YORK INTERNATIONAL9FORM 150.64-EG1residential or other similar sound-sensitive locations. Louvered Panels can be ordered for winter applications